S0000-TMB2
Thermostatic Mixing Valve with External Cold Water Bypass for Combination Station, 36 gpm
Specifications
Model S0000-TMB2 is a thermostatic mixing valve system for supplying tempered water to emergency fixtures and it shall have a tamperresistant factory set-point of 85°F, a paraffin based temperature element for long life and reliability, union strainer checkstops and an outlet thermometer. It shall include a dual internal cold water by-pass and a pressure based external by-pass to ensure flow in the event of a valve failure or loss of hot water supply. The valve shall provide precise temperature control, capable of compliance to the control accuracy requirements of ASSE 1017. It shall effectively shut down in the event of cold water failure.
Standard Equipment
Precise temperature control that meets the temperature control accuracy requirements of ASSE 1017
Dirt and lime resistant poppet and seat require minimal maintenance
Exclusive dual internal by-pass ensures cold water flow if hot water is lost or actuator fails
Triple duty checkstops (service stop, checks and strainers) are included
External system is pressure based and factory set to perform in most installations. Set-up can be customized for maximum system performance in both tempering and by-pass modes
Temperature set-point is factory set at 85°F and is tamper-resistant to prevent unauthorized changes
Maximum possible setting is limited to 95°F, minimum of 60°F
Large, easy to read dial thermometer
Loss of cold water results in the effective close off of the hot water supply
Complies with ANSI Z358.1-2004
No electrical requirements
OPERATING SPECIFICATIONS:
Maximum Pressure: 125 psi (861.25 kPA)
Maximum Hot Water Temperature: 180°F (82°C)
Approach Temperature: 15°F (8°C)
Temperature Adjustment Range: 60°F (15°C) to 95°F (35°C)
Factory Set Temperature: 85° (29°C)
Mixing Valves
| S0000-TMB1 |
| S0000-TMB2 |
| S0000-TMB3 |
| S0000-TMV1 |
| S0000-TMV2 |
| S0000-TMV3 |