S1360-HT
Heat Traced Combination Station, Eye/Face Wash Less Bowl, Plastic Showerhead
Specifications
Model S1360-HT is a heat traced, pedestal mounted combination station with an eye/face wash, less bowl, ABS plastic eye/face wash spray heads, an inline strainer and a stay-open 1/2" ball valve with a push handle and a shower with a plastic showerhead and 1" stay-open ball valve with a pull rod. Unit is insulated and encased in a molded ABS jacket with heat traced cable wrapped around the internal supply pipe with a thermostat to control the heating.
Standard Equipment
Showerhead: Yellow, ABS plastic 7-3/8" diameter showerhead with a 20 gpm flow regulator.Shower Valve: 1" IPS rough chrome plated brass stay-open ball valve. Unit is provided with a stainless steel actuator arm and a 29" stainless steel pull rod.
Spray Head Assembly: ABS yellow plastic eye/face wash heads with integral flip dust covers, internal flow controls and filters to remove debris from the water.
Eye/Face Wash Valve: 1/2" IPS chrome plated brass, stay-open ball valve with a stainless steel stem and push handle. An integrated weep hole drains residual water from the eye/face wash heads after each use.
Protection Valve: freeze protection valve that opens automatically in the event electrical failure causes internal water temperatures to drop below 35ºF.
Water Supply: 1-1/4" NPT female threaded top or bottom inlet.
Jacket/Insulation: 1" thick removable foam insulation covered by a UV protected ABS plastic jacket. All joints and openings are factory sealed.
Piping & Mounting: Schedule 40 internal galvanized steel piping and a 9-1/8" diameter cast iron floor flange.
Electrical System/Heat Cable: 120 VAC, 60 HZ single phase. Systems junction box and components are rated for Class 1, Division 2, Groups B, C and D. Self regulating heat tracing cable is controlled by a thermostat that shuts off the heat when the ambient temperature reaches 55°F. Cable is both FM and CSA approved.
Universal Sign: ANSI compliant, vertical identification sign.
Weekly Test Tag: A water proof test card to record the date and inspector's name for weekly functional testing of the unit.